N2 - Lumped capacitance models have been introduced to study transient thermal response of data centers. Chilled water interruption of a Computer Room Air Handling (CRAH) unit is one of several failure scenarios of data center cooling infrastructures. In such a scenario, predicting the transient thermal response of the CRAH unit depends requires the determination of the CRAH lumped capacitance model parameters: The thermal capacitance (thermal mass) and the time constant. In this paper, we propose an experimental methodology to extract sufficient information for the lumped capacitance modeling of CRAH units. The method requires measurements of inlet and exit air temperature, air flow rate and CRAH fan power. If the chilled water supply to a CRAH unit is intentionally interrupted in a data center with multiple redundant CRAH units, sufficient information to estimate the CRAH lumped capacitance parameters can be obtained without disturbing the data center operation.
AB - Lumped capacitance models have been introduced to study transient thermal response of data centers. Chilled water interruption of a Computer Room Air Handling (CRAH) unit is one of several failure scenarios of data center cooling infrastructures. In such a scenario, predicting the transient thermal response of the CRAH unit depends requires the determination of the CRAH lumped capacitance model parameters: The thermal capacitance (thermal mass) and the time constant. In this paper, we propose an experimental methodology to extract sufficient information for the lumped capacitance modeling of CRAH units. The method requires measurements of inlet and exit air temperature, air flow rate and CRAH fan power. If the chilled water supply to a CRAH unit is intentionally interrupted in a data center with multiple redundant CRAH units, sufficient information to estimate the CRAH lumped capacitance parameters can be obtained without disturbing the data center operation.
UR - http://www.scopus.com/inward/record.url?scp=84954067286&partnerID=8YFLogxK
UR - http://www.scopus.com/inward/citedby.url?scp=84954067286&partnerID=8YFLogxK
U2 - 10.1115/IPACK2015-48430
DO - 10.1115/IPACK2015-48430
M3 - Conference contribution
AN - SCOPUS:84954067286
T3 - ASME 2015 International Technical Conference and Exhibition on Packaging and Integration of Electronic and Photonic Microsystems, InterPACK 2015, collocated with the ASME 2015 13th International Conference on Nanochannels, Microchannels, and Minichannels
BT - Thermal Management
PB - American Society of Mechanical Engineers
T2 - ASME 2015 International Technical Conference and Exhibition on Packaging and Integration of Electronic and Photonic Microsystems, InterPACK 2015, collocated with the ASME 2015 13th International Conference on Nanochannels, Microchannels, and Minichannels
Y2 - 6 July 2015 through 9 July 2015
ER -