TY - GEN
T1 - Energy modeling of air-cooled data centers
T2 - ASME 2011 Pacific Rim Technical Conference and Exhibition on Packaging and Integration of Electronic and Photonic Systems, InterPACK 2011
AU - Demetriou, Dustin W.
AU - Khalifa, H. Ezzat
PY - 2011
Y1 - 2011
N2 - The work presented in this paper describes a simplified thermodynamic model that can be used for exploring optimization possibilities in air-cooled data centers. The model is used to parametrically evaluate the total energy consumption of the data center cooling infrastructure for data centers that utilize aisle containment. The analysis highlights the importance of reducing the total power required for moving the air within the CRACs, the plenum, and the servers, rather than focusing primarily or exclusively on reducing the refrigeration system's power consumption and shows the benefits of bypass recirculation in enclosed aisle configurations. The analysis shows a potential for as much as a 57% savings in cooling infrastructure energy consumption by utilizing an optimized enclosed aisle configuration with bypass recirculation, instead of a traditional enclosed aisle, where all the data center exhaust is forced to flow through the computer room air conditioners (CRACs), for racks with a modest temperature rise (∼10°C). However, for racks with larger temperature rise (> ∼20°C), the saving are less than 5%. Furthermore, for servers whose fan speed (flow rate) varies as a function of inlet temperature, the analysis shows that the optimum operating regime for enclosed aisle data centers falls within a very narrow band and that power reductions are possible by lowering the uniform server inlet temperature in the enclosed aisle from 27°C to 22°C. However, the optimum CRAC exit temperature over the 22-to-27°C range of enclosed cold aisle temperature falls between ∼16 and 20°C because a significant reduction in the power consumption is possible through the use of bypass recirculation. Without bypass recirculation, the power consumption for a server inlet temperature of 22°C enclosed aisle case with a server temperature rise of 10°C would be a whopping 43% higher than with bypass recirculation. It is worth noting that, without bypass recirculation maintaining the enclosed cold aisle at 22°C instead of 27°C would reduce power consumption by 48%. It is also shown that enclosing the aisles together with bypass recirculation (when beneficial) also reduces the dependence of the optimum cooling power on server temperature rise.
AB - The work presented in this paper describes a simplified thermodynamic model that can be used for exploring optimization possibilities in air-cooled data centers. The model is used to parametrically evaluate the total energy consumption of the data center cooling infrastructure for data centers that utilize aisle containment. The analysis highlights the importance of reducing the total power required for moving the air within the CRACs, the plenum, and the servers, rather than focusing primarily or exclusively on reducing the refrigeration system's power consumption and shows the benefits of bypass recirculation in enclosed aisle configurations. The analysis shows a potential for as much as a 57% savings in cooling infrastructure energy consumption by utilizing an optimized enclosed aisle configuration with bypass recirculation, instead of a traditional enclosed aisle, where all the data center exhaust is forced to flow through the computer room air conditioners (CRACs), for racks with a modest temperature rise (∼10°C). However, for racks with larger temperature rise (> ∼20°C), the saving are less than 5%. Furthermore, for servers whose fan speed (flow rate) varies as a function of inlet temperature, the analysis shows that the optimum operating regime for enclosed aisle data centers falls within a very narrow band and that power reductions are possible by lowering the uniform server inlet temperature in the enclosed aisle from 27°C to 22°C. However, the optimum CRAC exit temperature over the 22-to-27°C range of enclosed cold aisle temperature falls between ∼16 and 20°C because a significant reduction in the power consumption is possible through the use of bypass recirculation. Without bypass recirculation, the power consumption for a server inlet temperature of 22°C enclosed aisle case with a server temperature rise of 10°C would be a whopping 43% higher than with bypass recirculation. It is worth noting that, without bypass recirculation maintaining the enclosed cold aisle at 22°C instead of 27°C would reduce power consumption by 48%. It is also shown that enclosing the aisles together with bypass recirculation (when beneficial) also reduces the dependence of the optimum cooling power on server temperature rise.
UR - http://www.scopus.com/inward/record.url?scp=84860341578&partnerID=8YFLogxK
UR - http://www.scopus.com/inward/citedby.url?scp=84860341578&partnerID=8YFLogxK
U2 - 10.1115/IPACK2011-52003
DO - 10.1115/IPACK2011-52003
M3 - Conference contribution
AN - SCOPUS:84860341578
SN - 9780791844618
T3 - ASME 2011 Pacific Rim Technical Conference and Exhibition on Packaging and Integration of Electronic and Photonic Systems, InterPACK 2011
SP - 385
EP - 394
BT - ASME 2011 Pacific Rim Technical Conference and Exhibition on Packaging and Integration of Electronic and Photonic Systems, InterPACK 2011
Y2 - 6 July 2011 through 8 July 2011
ER -